Rack Notes #001 — The Backup Path Has to Carry the Load

AI data center briefing · Issue 001

Archive edition · Reporting window November 2–9, 2026 · Published November 26, 2026

Night-shift cutaway of a data center showing backup power, two fiber entrances, GPU racks with alternate network paths, coolant pipes, and an operator monitoring two fabrics.

A generator waiting for a start signal and a GPU job waiting on a failed path have something in common. Recovery depends on the capacity and control logic available after the failure.

01 · Incident response

Google’s backup generators missed the start signal

November 4 · Operator postmortem

During an October 20 outage in London, the primary utility feed failed while the other feed’s breaker was open for maintenance. Both generator controllers sensed voltage upstream of that open breaker and treated the disconnected feed as available. The generators missed their start signal, the UPS batteries ran down, and the failover surge strained other zones. Google reported 6 hours and 8 minutes of main impact.

In practice · Include the single-feed maintenance state in a controlled transfer exercise. Measure time from utility loss to critical-load transfer against the available UPS runtime.

Google Cloud incident report

02 · GPU networking

Oracle adds failover to collective traffic

November 6 · Generally available on supported OCI infrastructure

Oracle released its OCCL network plugin for supported RoCEv2 and InfiniBand configurations using NVIDIA NCCL or AMD RCCL. It can shift collective traffic toward less congested paths and recover supported link or NIC failures when a usable path survives. Full NIC failover with NCCL requires version 2.24.3 or later. Oracle’s own 128-node GB300 benchmark measured about 10% higher all-reduce bus bandwidth under the tested conditions.

In practice · In a canary job, confirm the plugin is active on every rank, then take a physical NIC offline in a controlled test. Record whether the job survives and how much tail step time and throughput change.

Oracle release · OCCL deployment guide

03 · Fiber and private connectivity

Northern Virginia adds an orderable AWS path through Lumen

November 5 · Lumen generally available · Equinix and Megaport in preview

AWS added Northern Virginia to its managed last-mile interconnect. Lumen customers across the continental United States can order service through the metro. AWS provisions four redundant links across two physically diverse locations and describes a 99.99% availability SLA up to the Direct Connect port.

In practice · Before booking two independent paths in your design, ask the carrier to identify shared conduits, building entrances, and meet-me rooms on the site-to-carrier segment. Test whether the surviving path can carry the expected traffic.

AWS service announcement · Lumen service details

04 · Cooling and rack density

ACT tests a megawatt-scale two-phase cooling unit

November 3 · Vendor lab validation

Advanced Cooling Technologies reported more than 1 MW of heat removal in system-level testing of its two-phase coolant distribution unit. The test program exercised changing thermal loads from 200 kW to 1.2 MW. The usable capacity at a particular site depends on the facility-water conditions and the rest of the loop.

In practice · Write acceptance criteria around the site’s worst-case water inlet temperature and pressure drop. Have the commissioning team verify the remaining cooling capacity with one unit unavailable.

ACT validation report

05 · Routing and switching

Hedgehog moves unnumbered BGP into the default fabric design

November 5 · Open Network Fabric 26.05 release notes

Hedgehog 26.05 makes unnumbered BGP the default on fabric and mesh links and lets a single deployment manage multiple fabrics. The published upgrade paths start at 26.03.x and 26.04.x. An interface-based neighbor model changes how the operations team identifies a session during a link incident.

In practice · Drop a leaf-to-spine link in staging. Verify that monitoring points to the affected interface, BGP converges, and the surviving equal-cost paths carry the expected traffic.

Hedgehog release notes

How much reserve does a zone failure justify?

Separate the recovery targets for inference and checkpointable training. Price the reserve needed to carry committed inference traffic after losing a zone, then compare reserving additional compute for training with queueing those jobs until capacity returns. Use delayed jobs and GPU-hours lost since the last checkpoint to compare the two designs.